 | Monitors and displays ambient temp, relative humidity, discharge pressure and condensate
temp. |
 | Floats head pressure to lowest optimum operating pressure to save energy. |
 | Controls up to 32 steps of water pumps and fans. |
 | Calculates and displays ambient wet bulb temp. |
 | Displays and controls on difference between condensate and wet bulb temps. |
 | Has manual or automatic operation feature, displays difference between actual and
saturation pressure, letting you know if air is in system. |
 | Simple selection of the pump and fan sequence. |
 | Simple selection of minimum operation discharge pressure set point for your system. |
 | Automatically raises discharge pressure set point for defrost cycle. |
 | Has adjustable deadband and set point to avoid excessive fan cycling. |
 | Alarms on high safety control set point violations. |
 | Unloads compressor as high discharge safety pressure is reached. |
 | Shuts down compressors when high discharge safety pressure is reached. |
 | Simple change of all condenser control parameters. |
 | Minimum pump operation temp protects against freeze-ups |
 | The 16CV controls
up to 16 single-speed, two-speed and variable speed fans, controlling any combination of pumps,
single-speed fans, two-speed fans and variable speed fans. |
 | The 16CV preferentially operates the variable-speed fans over single-speed
or two-speed fans. |
 | The 16CV has a password-protected screen to specify minimum fan speed. |
 | The 16CV controller automatically enters delays for the transition for
high speed to low speed fans. |
 | The 16CV controller has ladder logic control capability for 12 analog inputs, 16 digital inputs and 16
digital outputs, for miscellaneous control needs.
|