 | Controls up to 5 compressors with one or two suction pressures. |
 | Controls screw, recips, or rotary compressors in any combination. |
 | Automatically sequences compressors to their most efficient combination to
save energy. |
 | Automatically keeps the compressors operating near full capacity to save
energy. |
 | Controls up to 2 different suction control set points at different times of day. |
 | Starts, stops, loads, and unloads compressors. |
 | Suction pressure control within 1 PSIG of the set point. |
 | Unloads compressors as high discharge safety pressure is approached. |
 | Discharge pressure shuts down on high discharge safety. |
 | Displays compressor suction set point at whatever value you choose. |
 | Displays current compressor suction operating pressure. |
 | Displays compressor suction deadband at whatever value you choose. |
 | Displays compressor suction minimum operating pressure set point. |
 | Displays compressor manual or automatic control status. |
 | Displays acceptable power outage time for auto restart. |
 | Displays daily pressure offset times to control 2 separate daily suction set points. |
 | Displays the compressor sequence and load percent capacity status. |
 | Alarms on safety control set point violations. |
 | Alarms on high suction trap liquid level and shuts down compressors of affected stage. |
 | Monitors your ammonia sniffer and shuts down compressors if leak is in the eng. room. |
 | Adjusts for non-linear slide valve capacity. |
 | Logs compressor run time hours and alerts for planned maintenance. |
 | Monitors system kWh usage. |
 | Simple for operator to change compressor control parameters. |
 | Monitors and displays ambient temp, relative humidity, discharge pressure and condensate
liquid temp. |
 | Floats head pressure to lowest optimum operating pressure to save energy. |
 | Controls up to 8 water pumps or fans. |
 | Calculates and displays ambient Wet Bulb Temp. |
 | Displays and controls on difference between dry bulb and wet bulb temps. |
 | Has manual or automatic operation feature, displays difference between actual and
saturation pressure , letting you know if air is in system. |
 | Allows operator to make changes to the pump and fan sequence. |
 | Allows operator to set the minimum operation discharge pressure set point. |
 | Automatically raises discharge pressure set point for defrost cycle. |
 | Has adjustable dead band and step delay set point to avoid excessive fan cycling. |
 | Shuts down compressors when high discharge safety pressure is reached. |
 | Simple for operator to change all condenser control parameters. |
 | Minimum pump operation temp protects against freeze-ups. |
 | Ladder Logic portion can be used for miscellaneous control, such as pump packages,
lighting, floor warming, battery chargers, water chemistry control, etc. |
 | OMNI has 16 digital inputs and 16 analog inputs that can be used to control
16 digital outputs using ladder logic. |
 | Analog and digital inputs from compressor and condenser portion can also be used in logic. |
 | Ladder logic can use counting in logic. |
 | Ladder logic can use delays and time of day in logic. |
 | Ladder logic can use separately displayed adjustable set points in logic. |
 | Logic is written in easy to use English language tables. |
 | Three pages of logic tables are available in password protected region. |
 | 16 internal flags and 16 counters are available for use in logic. |